Preliminary investigations indicate that the fire originated from a faulty 33kV instrument transformer (CT/VT) installed by Egbin Power Plc. The faulty equipment, part of the power station’s service transformer, is directly connected to the 33kV side of TCN’s transformer. The resulting fire caused significant damage, including a rupture to the main tank of TCN’s 150MVA transformer, leading to oil leakage.
As a consequence, there has been a temporary reduction in bulk power supply to the Ikorodu and Odogunyan 132/33kV Transmission Substations, which feed parts of the IKEDC and IBEDC franchise areas. Additionally, Sagamu Lines 1 and 2, as well as Maryland Line 2, on the 132kV network within Lagos State, have been impacted.At the time of the incident, a total load of 47MW was affected. This load was promptly transferred to the second available 150MVA transformer within the substation, which is currently operating under strain. Unfortunately, the capacity deficit has since increased, resulting in continued load-shedding across all affected areas.